APC Smart-UPS RT 1000VA, 230V, 6x IEC 60320 & 2x IEC Jumpers outlets


Specifications


Input
network frequency50/60 Hz +/- 5 Hz auto-sensing
input voltage limits160...280 V
Output
Maximum configurable power in W700 W
harmonic distortionLess than 3 %
output frequency50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
crest factor3 : 1
UPS typeDouble conversion online
Wave typeSine wave
bypass typeBuilt-in bypass
Maximum configurable power in VA1000 VA
Batteries & Runtime
Run TimeView Runtime Graph
action_new_window
EfficiencyView Efficiency Graph
action_new_window
number of battery filled slots1
number of battery free slots0
Battery recharge time3 h
number of battery replacement quantity1
additional informationConfigurable for 220 : 230 or 240 nominal output voltage
battery charger power109 W rated
Battery power in VAH328 VAh runtime
battery life3…5 year(s)
battery optionSURT48XLBP 1 984 VAh
SURT48XLBP 2 1640 VAh
SURT48XLBP 3 2296 VAh
SURT48XLBP 4 2952 VAh
SURT48XLBP 5 3608 VAh
SURT48XLBP 6 4264 VAh
SURT48XLBP 8 5576 VAh
SURT48XLBP 10 6888 VAh
extended runtime1