เปลี่ยนแบตเตอรี่ SUVTP40KH4B4S

เปลี่ยนแบตเตอรี่ SUVTP40KH4B4S

  รายละเอียด

เปลี่ยนแบตเตอรี่ SUVTP40KH4B4S

APC Smart-UPS VT 40kVA 400V w/4 Batt. Mod., Start-Up 5X8, Internal Maint Bypass, Parallel Capability


Specifications


Input
network frequency40...70 Hz auto-sensing
number of input connectors1 hard wire 5-wire (3P + N + E)
input voltage limits304...477 V
maximum input current55 A
switching current capacity80 A
Input Power Factor at Full Load0.98
Output
Maximum configurable power in W32000 W
harmonic distortionLess than 5 % at full load
output frequency47...53 Hz for 50 Hz nominal sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
crest factor3 : 1
UPS typeDouble conversion online
Wave typeSine wave
bypass typeBuilt-in maintenance bypass
Built-in static bypass
maximum output current64 A
Maximum configurable power in VA40000 VA

Batteries & Runtime
Run TimeView Runtime Graph
action_new_window
EfficiencyView Efficiency Graph
action_new_window
number of battery filled slots4
number of battery free slots0
Battery recharge time5 h
number of battery replacement quantity4
additional informationConfigurable for 380 : 400 or 415 V 3 Phase nominal output voltage
battery voltage+/- 192 V (split battery referenced to neutral)
discharge battery voltage+/- 154 V
battery charger power1985 W rated
Battery power in VAH9943 VAh runtime
battery life3…5 year(s)
battery optionSUVTXR2B6S 1 14848 VAh
SUVTXR6B6S 1 24609 VAh
SUVTXR6B6S 2 39152 VAh
SUVTXR6B6S 3 54017 VAh
SUVTXR6B6S 4 68749 VAh
Battery graph commentsEstimated runtimes based on battery vendor data, at typical environmental conditions, with no electrical input and balanced PF = 0.8 output.
extended runtime1

  • รหัสสินค้า: SUVTP40KH4B4S
  • สถานะ: มีสินค้าในสต๊อก
  • 0.00€