เปลี่ยนแบตเตอรี่ GVMPB200KHS

รายละเอียด
เปลี่ยนแบตเตอรี่ GVMPB200KHS
Galaxy VM 200 kVA UPS Parallel 400-400 V with Backfeed protection, Start up 5x8
Specifications
Input| network frequency | 40...70 Hz |
|---|
| input voltage limits | 250...600 V adjustable 320...456 V 380 V 320...480 V 400 V 320...498 V 415 V |
|---|
| maximum input current | 328 A |
|---|
| switching current capacity | 400 A |
|---|
| max short time withstand current | 65 kA |
|---|
| input harmonic distortion | Less than 3 % for full load |
|---|
| input protection type | GL fuse |
|---|
| inrush current | 200 A peak |
|---|
| load power factor | 0.5 leading to 0.5 lagging |
|---|
| Input Power Factor at Full Load | 1 |
|---|
Output| Maximum configurable power in W | 180 kW |
|---|
| harmonic distortion | Less than 2 % |
|---|
| output frequency | 50/60 Hz +/- 1 Hz sync to mains 50/60 Hz +/- 1 Hz unsynchronised |
|---|
| crest factor | Unlimited |
|---|
| Wave type | Sine wave |
|---|
| output voltage tolerance | +/- 1% static and +/- 3% at 100% load step |
|---|
| output harmonic distortion | < 2% linear load and < 3% non-linear load |
|---|
| output overload operation | 10 minutes at 125% and 60 seconds at 150% |
|---|
| neutral output current | 289 A |
|---|
| bypass type | Built-in static bypass |
|---|
| Maximum configurable power in VA | 200 kVA |
|---|
Batteries & Runtime| Efficiency | View Efficiency Graph action_new_window |
|---|
| battery voltage | 480 V |
|---|
| discharge battery voltage | 384 V |
|---|
| max current discharge | 393 A |
|---|
| Battery power in VAH | 0 VAh runtime |
|---|
| extended runtime | 0 |
|---|
- รหัสสินค้า: GVMPB200KHS
- สถานะ: มีสินค้าในสต๊อก